4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
071 Entry to follow behaviour on internal
active (C)
To change the zone property of the entry to follow zone at
internal active (C):
1. On the control unit, enter:
071
2. The LCD display shows: 071: C=ER =ER
3. Via the keypad, select from the following items
and press:
0
C=ER =ER
A zone programmed as entry to follow
keeps this property even during internal
activation and permits entry to this zone
during the entry delay period.
1
C=FE = FE
A zone programmed as entry to follow
changes its zone property during
internal activation to entry/exit and
starts the delay time if the zone triggers
and during active internal activation.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
072 Behaviour of exit mode internal (C)
To change the property of the exit mode for internal active
(C):
1. On the control unit, enter:
072
2. The LCD display shows: 072: C=Low Tone
3. Via the keypad, select from the following items
and press:
0
C=Low Tone
The acoustic signal during the exit
delay time is emitted at half volume.
1
C=Instant
During internal activation, the alarm
centre is internally activated
immediately – i.e., without delay.
2
C=Silent
No acoustic signal is emitted during the
delay time. Following expiry of the delay
time, the alarm centre emits a brief
signal.
3
C=A
The initial mode for internal active B is
as for the initial mode of overall active A
In a partitioned system
0
C=Timed
Activation of partition C after exit time
(command 75). A connected key switch
at the control unit shortens the exit time
when activated
1
C=Terminated
Activated via key switch connected to
the control unit. The exit time is
unlimited.
2
C=Final Door
Activation of the partition by closing a
last door detector
3
C=Instant
Active without delay time
4
C=Silent
Use command 75 for the exit time. The
control unit emits a double beep when
the time has expired.
5
C=Lock Set